Honeywell Notifier Fire Alarm Relay Module – FRM-1
Features
- Automatic type identification for seamless device recognition by the control panel.
- Powered by the two-wire SLC loop, with internal circuitry and relay; the FCM-1(A) module requires additional power for horns, strobes, etc., or audio for speakers.
- An integral LED blinks green for each communication received from the control panel and turns steady red upon activation.
- Option to globally deselect the LED blink feature, affecting all devices.
- Equipped with high noise immunity to EMF/RFI.
- The FCM-1(A) is capable of switching 24-volt NAC power and audio (up to 70.7 Vrms).
- Features a wide viewing angle for the LED.
- Includes SEMS screws with clamping plates for simplified wiring.
- Allows direct-dial entry for addresses 01–159 in FlashScan loops and 01–99 in CLIP mode loops.
- Supports wiring for Class B or A (Style Y or Z) for speakers, and audible/visual applications.
Specifications
| Weight | 0.4 lbs |
| Dimensions | 4.00 × 4.50 × 2.00 in |
| Manufacturer | Honeywell |
| Brand | Notifier |
| Condition | New |
| Type | Intelligent Module |
| Style | Control, Relay |
| Programming | Rotary Dials |
| Protocol | CLIP, FlashScan |
| Production Status | Active |